DETAILED DESCRIPTION: 
                            
	PRODUCT DESCRIPTION
	The input-output Device FD7203 – 10 inputs / 16 outputs is designated to produce and send an electrical signal to various devices (lift doors, fans, etc.) in the case of an events and recording external impacts typical for a fire condition or other events. It is compatible with addressable fire control panels IFS7002, supplementing the possibilities of the address systems series IFS7000. 
	 
	Technical Data 
	Address loop: 
	– supply voltage: (15÷30)V DC 
	– current consumption in duty mode: < 350µA 
	– current consumption in alarm state: (3±1)mA 
	Power loop: 
	– supply voltage: (12÷30)V DC 
	– current consumption in duty mode: < 35mA 
	– current consumption in alarm state: up 1A 
	Inputs: 10 pcs 
	Electroplated separated programmable: 8 pcs 
	– activation voltage: (5÷30)V DC 
	Monitored inputs programmable: 2 pcs 
	– maximal resistance of the loop: 100 Ω 
	– short circuit: R input<0,5kΩ 
	– activated input: 0,6kΩ – duty mode: 1,5kΩ – interruption: 4,8kΩ – end of line element: 3,6kΩ 
	Outputs: 16 pcs 
	Relay with programmable functions: 3 pcs 
	– type: potential free, switching with programmable functions 
	– power supply specifications: 30V DC/1A; 125VAC/0,5A 
	Monitored with programmable functions: 2 pcs 
	– type: Potential 
	– power supply specifications: (12÷30)V DC 
	– peak activation current: 150 mA 
	– end of line element: 1,0 kΩ 
	Open collector with programmable functions: 11 pcs 
	– peak voltage at the output: 30V DC 
	– peak activation current: 35 mA 
	Operational temperature range: from minus 5°С to 40°С 
	Relative humidity resistance (no condensation): ≤95% 
	Dimensions: (313х218х85) mm 
	Weight: 1.170 kg 
                             |