English Việt Nam
PRODUCT CATEGORY
NEW NEWS
View all
INFORMATION
Showtimes in theaters
Exchange
Quotes
Gold price information
Lotto Results
ADVERTISING
 
6100 Single Loop Fire Alarm Panel
  • Cost Effective Single Loop Panel
  • High Capacity Loop - 192 Addresses
  • Algo-Tec™ 6000PLUS Protocol
  • Surface and Recessed Mounting
  • Easy to Install
  • Reduced False Alarms
  • Enhanced Performance
  • On Site Flexibility
  • Designed to EN 54-2 & 4
   DETAILED DESCRIPTION:

 

Rated Voltage

100 to 240V ac rms

Rated Frequency

50 to 60 Hz

Rated Current

600mA rms

Working Voltage

21.5 - 29V dc

Temperature Range

0 - 40°C

Maximum Humidity

85% Non-condensing

IP Rating

IP30

Battery Type

2 x 12V 3.3Ah sealed lead acid

Standby Load
(Mains Fail Condition) 

22mA

Maximum Alarm Load
(Mains Fail Condition)

56mA panel
600mA loop
200mA conventional alarms (100mA per alarm output)
150mA auxillary 24V output
20mA fire-link

Display

Backlit liquid crystal display 4 lines of 20 characters

Digital Addressable Loops

1 loop, with 192 address capacity
Algo-Tec™ 6000PLUS Protocol

Total Loop Load

600mA including all loop connected devices

Zones

32 Zones, 16 with LED indication, plus general fire indicator

Integral Charger

1A dc switch mode, temperature compensated

Integral Battery

2 x 12V 3.3Ah sealed lead acid

Alarm Outputs

2 monitored conventional sounder circuits
(100mA per output maximum)   

Up to 192 alarm outputs using loop output devices.

Global Fire Outputs

1 set of non-monitored changeover contacts
(1A @ 24V dc) operating on any fire

Alarm Load

600mA loop, 100mA per conventional alarm output

Fault Monitoring

Fully fault monitored to EN 54-2 & 4

Fault Output

Single pole changeover contacts
(1A rated @ 24V dc)

Auxiliary Output Supply

24V dc fused at 150mA

Common Fire Output
(fire station)

24V dc fully monitored output
(requires end of line module SF4165759)

Communications Interface

USB 2.0 (Type A male to Type B male connection lead required - 2 Metres maximum length)

Dimensions (mm)

228(W) x 345(H) x 111(D)

Weight  

1.5kg (excluding batteries)

Applicable Standards

EN 54-2 : 1997 + A1 : 2006
EN 54-4 : 1998 + A1 + A2

 

   DOWNLOAD:
CONTACT ORDER
OTHER PRODUCTS
OPH 120
Remote control panel IFS7002R
SENTINEL 8×8
 
ONLINE SUPPORT
Technical Support
Hotline: 0838 404 901
Business Support
Do Huy Duong: 090 3848 989
PARTNER
STATISTICS
Online: 23
Total access: 2590333
Copyright 2008 - 2012 by PCCC4-10 company - Designed by EATech Corp