Power Supply Mains
|
230V AC. Nominal (+/- 10%)
|
Integral Charger
|
1A switch mode, temperature compensated
|
Auxiliary 24V output
|
24V DC, 100mA max
|
Maximum Battery Size
|
2 x 12V 3.3Ah
|
Mains Fuse
|
1A HRC ceramic 20mm
|
Battery Fuse
|
1.6A F 20mm
|
Working Voltage
|
20V to 30V DC
|
Current Consumption
|
15mA (24V DC) + Zone Load
|
Number of Detector Zones
|
8
|
Maximum Zone Cable Length
|
500 metres
|
Maximum Zone Cable Capacitance
|
0.27μF
|
Maximum Zone Cable Resistance
|
15Ω per conductor
|
Detector Circuit EOL Values
|
Resistive (8.2kΩ) or capacitive (100μF+22Ω)
|
Maximum Quiescent Zone Load
|
1.5mA per zone
|
Maximum Number of Detectors
|
20 per zone (smoke or heat)
|
Maximum Number of Devices
|
32 (MCP and Dets) per zone
|
MCP Series Resistor Value
|
180Ω +/- 5%
|
Number of Alarm Circuits
|
4
|
Alarm Circuit End Of Line Value
|
10kΩ 1/4W +/- 5%
|
Maximum Alarm Load
|
150mA per circuit
|
Class Change Input
|
Activates alarm outputs
|
Remote Alarm Input
|
Activates alarm outputs, internal buzzer and general fire indicator
|
Global Fault Contacts
|
24V DC 1 A rating
|
Global Fire Contacts
|
24V DC 1 A rating
|
Expansion Port Communications
|
2 wire Data + 2 wire Power
|
Temperature Range
|
0 to 40 Degrees Centigrade
|
Humidity Limit
|
85% Non-Condensing
|
Dimensions (mm)
|
387(W) x 242(H) x 95(D)
|