Nút nhấn khẩn chống nước 3000/MCP/WP
   DETAILED DESCRIPTION:

Environment

-10 to 50ºC, 95% R.H
(non condensation or icing)

Ingress Protection

EN54-23 Type B Outdoor + IP65

Weight (excluding base)

315g

Loop Powered

Yes

Voltage

18 - 28V

Loop Standby Load

0.7mA

Peak Loop Alarm

24mA

Mounting Height (x)

2.4 metres

Coverage (y)

7m configurable to 3m

Coverage Volume Code

W-2.4-7 (117.6m³)

Flash Rate

0.5Hz white flash

Isolator

Yes

Dimensions (mm)

132(H) x 91(D) x Ø114

Product Approval

CoCP No: 0359-CPR-0409
DoP No: PFD-CPR-0102
Relevant Standard: EN54 Part 3, 17 & 23
CE Marked

 

 

   DOWNLOAD: