Module 3 inputs / 6 outputs FD7203

It is designed to perform control over external devices for the fire alarm system IFS7000 in Duty mode and upon detection of Fire Condition. The module is power supplied via the power loop, and it is controlled via the signal loop. The built-in short circuit isolators are available.

It satisfies the requirements of the European Standard EN54-17 & EN54-18.

   DETAILED DESCRIPTION:

Technical data
INPUTS: 3 separated by galvanization
OUTPUTS: 6
– 1 controllable: (11-30)VDC/200mA
– 4 relay, switching: over 1A/30VDC 0.5A/125VAC
– 1 for auxiliary supply: (12-30) VDC/1A

SUPPLY VOLTAGE:
– Signal loop: (15-30) VDC
– Power loop: (12-30) VDC

ACTIVATED STATE CURRENT:
– Signal loop: 3mA
– Power loop: Up to 1A
DEGREE OF PROTECTION: IP 50
OPERATING TEMPERATURE: Minus 10oC to 55oC
RELATIVE HUMIDITY: (93±3) % at 40oC
DIMENSIONS: 120 x 164 x 74 mm
WEIGHT: 0.250 kg