Module 4 Input/Output 6000/4IO

The Protec 4 way input/output interface is a auxiliary powered input / output device providing 2 local zones of conventional detectors, 2 monitored inputs, 2 local monitored alarm outputs and two volt free changeover contacts. The contacts may be used to connect to ancillary equipment.

   DETAILED DESCRIPTION:

Loop protocol

Protec Algo-tec™ 6000 MX1

Loop isolator fitted

Yes, on board (consult Protec DEL2110 for details)

Loop voltage range

18 to 28V peak loop

Number of loop addresses used

4 maximum, user and build configurable

24V Auxiliary input voltage range

18 to 28V dc

Environmental operational limits

-10 to 50ºC (maximum 95% RH no condensation or icing)

Loop quiescent current (24V loop peak)

0.6mA

Loop alarm current (average)

0.6mA

Zone short circuit current (24V)

26mA peak ± 2mA

Zone end of line requirements (I/P 1 & I/P 2)

Resistive - 8.2k ±5% ¼W, Capacitive - 100μ F ±20% in series with 22Ω ±5% ¼W

Input cabling requirements

Maximum cable resistance 6Ω per conductor
Maximum cable capacitance 0.2μ F between cable conductors

Zone quiescent current

500μ A maximum ( 10 Protec 3000 detectors per zone )

Zone reset time

2 seconds, with active zone discharge

Manual Call Point requirements

Must be fitted with a series 330Ω or 180Ω resistor

Zone short circuit threshold

Below 5% of supply voltage

Zone fire threshold

Below 70% of supply voltage

Zone resistive open circuit threshold

Above 92% of supply voltage

Monitored input end of line details

End of line resistor value 47kΩ 1/4W ±5%

Monitored input short circuit threshold

Below 230Ω

Monitored input fire threshold

Below 7.85kΩ

Monitored input pre-alarm threshold

Below 32kΩ ( Input 3 only )

Monitored input open circuit threshold  

Above 111kΩ

Sounders supported

Protec 3000 series

Sounder circuit end of line

10kΩ ¼W ±5%

Sounder circuit cable requirements

Maximum cable resistance depends on Volt drop calculations
Maximum cable capacitance 0.1 F between cable conductors.

Sounder short circuit fault threshold

Below 2kΩ

Sounder open circuit fault threshold

Above 18kΩ

Sounder current limit (maximum)

1.6A

Sounder circuit fuses

20mm x 5mm 1.6A Quick Blow

Clean contact output details

1 Single pole changeover rated for 2A maximum at 24V dc ( non inductive )
1 Single pole changeover rated for 5A maximum at 230V ac ( non inductive )

Weight

245g ( including din rail housing, no backbox, 4 way build )

LED Indicator

Use only high brightness LED (Protec stock code: NK 02-676-46)

 

   DOWNLOAD:
CONTACT ORDER
OTHER PRODUCTS
EHL 800 / CX / CXT
Mares Console - Mission 2 - SPG and Depth
Rescue Ladder Vehicle (Finland)
 
ONLINE SUPPORT
Technical Support
Hotline: 0838 404 901
Business Support
Do Huy Duong: 090 3848 989
PARTNER
STATISTICS
Online: 15
Total access: 3078600
Copyright 2008 - 2012 by PCCC4-10 company - Designed by EATech Corp