English Việt Nam
PRODUCT CATEGORY
NEW NEWS
View all
INFORMATION
Showtimes in theaters
Exchange
Quotes
Gold price information
Lotto Results
ADVERTISING
 
Trung Tâm Xả Khí EXT 301

Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the extinguishant releasing panel offers outstanding value and performance for all small and medium fixed firefighting installations.

With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.

The extensive configuration options of the panel allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-01)

The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety. The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.

With all of the electronics mounted on a single, easily removable, steel plate panels are both robust and easy to install.

   DETAILED DESCRIPTION:

Size (surface)

385W x 310H x 90D (mm)

Size (flush)

500mA switch mode, temperature compensated

Mains supply

24V DC, 100mA max

Mains supply fuse

2 x 12V 2.2Ah

Power supply rating

1A HRC ceramic 20mm

Panel in current mains fail

1A F 20mm

ROV output

20V to 30V DC

Sounder outputs

15mA (24V DC) + Zone Load

Fault relay contact rating

2

Fire relay contact rating

500 metres

Lcl fire relay contact rating

30VDC 1A Amp max

First stage contact rating

30VDC 1A Amp max

Second stage contact rating

30VDC 1A Amp max

Extract contact rating

30VDC 1A Amp max

Zone quiescent current

2mA maximum

Detection circuit EOL

6K8 5% 1/2 Watt resistor

Monitored input EOL

6K8 5%1/2 Watt resistor

Sounder circuit EOL

10K 5% 1/4 Watt resistor

Extinguishant output EOL

1N4004 Diode

No. of detection circuits

3

No. of sounder circuits

2 x 1st Stage, 1 2nd Stage

Ext release output

Fused at 1 Amp

Ext release delay

Adjustable 0 to 60 Secs

Ext release duration

Adjustable 60 to 300 Secs

Status unit

Two wire RS485 connection

Status unit power output

Fused at 500mA with Fuse

 

   DOWNLOAD:
CONTACT ORDER
OTHER PRODUCTS
Module 6000/2APZA
6100 Single Loop Fire Alarm Panel
VIRP
 
ONLINE SUPPORT
Technical Support
Hotline: 0838 404 901
Business Support
Do Huy Duong: 090 3848 989
PARTNER
STATISTICS
Online: 5
Total access: 2558820
Copyright 2008 - 2012 by PCCC4-10 company - Designed by EATech Corp