					Power Supply Mains | 
					230V AC. Nominal (+/- 10%) | 
		
			| 
					Integral Charger | 
					1A switch mode, temperature compensated | 
		
			| 
					Auxiliary 24V output | 
					24V DC, 100mA max | 
		
			| 
					Maximum Battery Size | 
					2 x 12V 3.3Ah | 
		
			| 
					Mains Fuse | 
					1A HRC ceramic 20mm | 
		
			| 
					Battery Fuse | 
					1.6A F 20mm | 
		
			| 
					Working Voltage | 
					20V to 30V DC | 
		
			| 
					Current Consumption | 
					15mA (24V DC) + Zone Load | 
		
			| 
					Number of Detector Zones | 
					4 | 
		
			| 
					Maximum Zone Cable Length | 
					500 metres | 
		
			| 
					Maximum Zone Cable Capacitance | 
					0.27μF | 
		
			| 
					Maximum Zone Cable Resistance | 
					15Ω per conductor | 
		
			| 
					Detector Circuit EOL Values | 
					Resistive (8.2kΩ) or capacitive (100μF+22Ω) | 
		
			| 
					Maximum Quiescent Zone Load | 
					1.5mA per zone | 
		
			| 
					Maximum Number of Detectors | 
					20 per zone (smoke or heat) | 
		
			| 
					Maximum Number of Devices | 
					32 (MCP and Dets) per zone | 
		
			| 
					MCP Series Resistor Value | 
					180Ω +/- 5% | 
		
			| 
					Number of Alarm Circuits | 
					4 | 
		
			| 
					Alarm Circuit End Of Line Value | 
					10kΩ 1/4W +/- 5% | 
		
			| 
					Maximum Alarm Load | 
					150mA per circuit | 
		
			| 
					Class Change Input | 
					Activates alarm outputs | 
		
			| 
					Remote Alarm Input | 
					Activates alarm outputs, internal buzzer and general fire indicator | 
		
			| 
					Global Fault Contacts | 
					24V DC 1 A rating | 
		
			| 
					Global Fire Contacts | 
					24V DC 1 A rating | 
		
			| 
					Expansion Port Communications | 
					2 wire Data + 2 wire Power | 
		
			| 
					Temperature Range | 
					0 to 40 Degrees Centigrade | 
		
			| 
					Humidity Limit | 
					85% Non-Condensing | 
		
			| 
					Dimensions (mm) | 
					387(W) x 242(H) x 95(D) 
					  |