Loop protocol
|
Protec Algo-tec™ 6000 MX1
|
Loop isolator fitted
|
Yes, on board (consult Protec DEL2110 for details)
|
Loop voltage range
|
18 to 28V peak loop
|
Number of loop addresses used
|
2 maximum, user and build configurable
|
24V Auxiliary input voltage range
|
18 to 28V dc
|
Environmental operational limits
|
-10 to 50ºC (maximum 95% RH no condensation or icing)
|
Loop quiescent current (24V loop peak)
|
1.6mA + zone end of line current + zone loading
|
Loop alarm current (average)
|
18mA
|
Zone short circuit current (24V)
|
26mA peak ± 2mA
|
Zone end of line requirements (I/P 1 & I/P 2)
|
Resistive - 8.2k ±5% ¼W, Capacitive - 100μ F ±20% in series with 22Ω ±5% ¼W
|
Input cabling requirements
|
Maximum cable resistance 6Ω per conductor
Maximum cable capacitance 0.2μ F between cable conductors
|
Monitored input end of line details
|
End of line resistor value 47kΩ 1/4W ±5%
|
Monitored input short circuit threshold
|
Below 230Ω
|
Monitored input fire threshold
|
Below 7.85kΩ
|
Monitored input pre-alarm threshold
|
Below 32kΩ ( Input 3 only )
|
Monitored input open circuit threshold
|
Above 111kΩ
|
Clean contact output details
|
1 Single pole changeover rated for 2A maximum at 24V dc ( non inductive )
1 Single pole changeover rated for 5A maximum at 230V ac ( non inductive )
|
Weight
|
245g ( including din rail housing, no backbox, 4 way build )
|
LED Indicator
|
Use only high brightness LED (Protec stock code: NK 02-676-46)
|