Power Supply Mains
|
100V-240V ac
|
Integral Charger
|
600mA
|
Auxiliary 24V output
|
24V dc, 150mA max
|
Maximum Battery Size
|
2 x 12V 2.2Ah
|
Mains Fuse
|
16A time delay (not replaceable)
|
Battery Fuse
|
1.6A resettable fuse
|
Working Voltage
|
18V to 30V DC
|
Current Consumption
|
22mA (24V DC) + Zone Load
|
Number of Detector Zones
|
2 (3502), 4 (3504), 8 (3508)
|
Max Zone Cable Length
|
500 metres
|
Max Zone Cable Capacitance
|
0.25µF
|
Max Zone Cable Resistance
|
15Ω per conductor
|
Detector Circuit EOL Values
|
Resistive(8.2Ω) or capacitive (100µF+22Ω)
|
Max Quiescent Zone Load
|
5mA per zone
|
Max Number of Detectors
|
25 per zone (smoke or heat)
|
Maximum Number of Devices
|
32 (MCP and Dets) per zone
|
MCP Series Resistor Values
|
180Ω ±5%
|
Number of Alarm Circuits
|
2
|
Alarm Circuits EOL Value
|
10kΩ ±5% ¼W
|
Maximum Alarm Load
|
400mA per circuit
|
Class Change Input
|
Activates alarm outputs
|
Global Fault Contacts
|
24V DC 1 A rating
|
Global Fire Contacts
|
24V DC 1 A rating
|
Temperature Range
|
-5 to 40°C
|
Humidity Limit
|
95% Non-Condensing
|
Repeat Panel Operating Current
|
15mA (Standby), 30mA (Alarm) at 24V DC
|
Dimensions (mm)
|
228(W) x 345(H) x 111(D)
|