Loop protocol
|
Protec Algo-tec™ 6000 MX1
|
Loop isolator fitted
|
Yes, on board (consult Protec DEL2110 for details)
|
Loop voltage range
|
18 to 28V peak loop
|
Number of loop addresses used
|
2 maximum, user and build configurable
|
24V Auxiliary input voltage range
|
18 to 28V dc
|
Environmental operational limits
|
-10 to 50ºC (maximum 95% RH no condensation or icing)
|
Loop quiescent current (24V loop peak)
|
0.6mA
|
Loop alarm current (average)
|
0.6mA
|
Zone short circuit current (24V)
|
26mA peak ± 2mA
|
Zone end of line requirements (I/P 1 & I/P 2)
|
Resistive - 8.2k ±5% ¼W, Capacitive - 100μ F ±20% in series with 22Ω ±5% ¼W
|
Input cabling requirements
|
Maximum cable resistance 6Ω per conductor
Maximum cable capacitance 0.2μ F between cable conductors
|
Zone quiescent current
|
500μ A maximum ( 10 Protec 3000 detectors per zone )
|
Zone reset time
|
2 seconds, with active zone discharge
|
Manual Call Point requirements
|
Must be fitted with a series 330Ω or 180Ω resistor
|
Zone short circuit threshold
|
Below 5% of supply voltage
|
Zone fire threshold
|
Below 70% of supply voltage
|
Zone resistive open circuit threshold
|
Above 92% of supply voltage
|
Sounders supported
|
Protec 3000 series
|
Sounder circuit end of line
|
10kΩ ¼W ±5%
|
Sounder circuit cable requirements
|
Maximum cable resistance depends on Volt drop calculations
Maximum cable capacitance 0.1μ F between cable conductors
|
Sounder short circuit fault threshold
|
Below 2kΩ
|
Sounder open circuit fault threshold
|
Above 18kΩ
|
Sounder current limit (maximum)
|
1.6A
|
Sounder circuit fuses
|
20mm x 5mm 1.6A Quick Blow
|
Weight
|
245g ( including din rail housing, no backbox, 4 way build )
|
LED Indicator
|
Use only high brightness LED (Protec stock code: NK 02-676-46)
|